|
Posted by StickThatInYourPipeAndSmokeIt on July 6, 2009, 4:32 am
Please log in for more thread options On Sun, 05 Jul 2009 20:30:37 -0400, Jamie
>StickThatInYourPipeAndSmokeIt wrote:
>
>>
>>
>>>>Assuming a nominal 240VAC supply, 245V is in no way "not correct" -- it's
only
>>>>about a 2% overvoltage.
>>>
>>>And since there is likely no load in shop when the install was taking
>>>place, the 245 would be a higher than normal reading.
>>
>>
>> You're nuts. Maybe at the end of a 100 yard long run. Maybe.
>>
>> There is no reason, however, for the entire feed to a building to sag
>> that far between loaded and unloaded.
>it's most likely the feed to the building is 480/460 and a transformer
>is being used.
> I don't know to many electric companies that will supply 240 3 phase
>any more.
>
> I'd be willing to bet that the transformer came along with the move and
>that being the case, yes, it can sag abit when other equipment get going
>because I can't picture a huge xformer in use here.
>
>
More guess as you go bullshit.
|